3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool.
SUBMIT AN ERN FOR THE REPLACEMENT OF THE DISINFECTION FEEDER.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required pressure gauge was not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR/REPLACE THE FILTER PRESSURE GAUGE. Correct By: 14-Jul-2023
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FLOW METER.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gates or doors were not self-closing and lockable.
Repair gates or doors in order to be self-closing and lockable.
ADJUST THE GATE SO THAT IT SELF-CLOSES. Correct By: 21-Jul-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 14-July-2023
Comments |
---|
MAXIMUM ALLOWABLE WATER TEMPERATURE IS 90 DEGREES. IF NECESSARY TURN THE TEMPERATURE OF THE HEATER DOWN. Equipment requiring ODH plan approval has been replaced since the inventory report dated 6-28-21 without submitting an ERN to ODH. The disinfection feeder pump Stenner 45M5 was replaced with a FlexFlo A1N30A-7T. USED CHEMICAL BUCKETS SHOULD NOT BE REUSED. DO NOT USE AN EMPTY CHEMICAL BUCKET AS AN ACID TANK. LIFEGUARD MUST KEEP A CPR MASK WITH THEM WHEN ON DUTY. |