3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Corrected During Inspection Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
MANAGER ADJUSTED THE AUTOMATIC CHEMICAL CONTROLLER AT THE TIME OF INSPECTION. AFTER 45 MINUTES THE FREE CHLORINE LEVEL WAS MEASURED AT 3.2 PPM. Correct By: 12-Jul-2022
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
IF THE FLOW METER CANNOT BE REPAIRED, INSTALL A PRESSURE AND VACUUM GAUGE WITH A PUMP CURVE TO DETERMINE THE FLOW RATE.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN LADDERS Correct By: 19-Jul-2022
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 13-Jul-2022
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST ALKALINITY Correct By: 13-Jul-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 12-July-2022