3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW RATE TO AT LEAST 76 GPM. Correct By: 27-Jul-2018
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Repeat Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
LABEL THE OUTSIDE OF THE CHLORINE TANK STORAGE CAGE SO IT CAN BE QUICKLY AND EASILY IDENTIFIED. Correct By: 30-Jul-2018
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH LEVEL TO BETWEEN 7.2 AND 7.8. Correct By: 25-Jul-2018
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE THE ALKALINITY TO AT LEAST 60 PPM. Correct By: 25-Jul-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 23-July-2018
Comments |
---|
Corrections that have been made since the last inspection dated 6-5-18 -new main drain cover (Waterway 640-472xV) has been replaced on 7-1-2018. The drain cover has a 7 yr life span and must be replaced before 7-1-2025. -a sign stating WARNING NO LIFEGUARD AND SWIMMING ALONE IS NOT RECOMMENDED are posted -an air gap is on the filter backwash line -a test kit containing all the required reagents is available. I was not able to determine if the ASSE 1013 backflow preventer had been inspected. I forgot to check, but the SVRS (Emotron) must be tested and recorded monthly. |