3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
THIS IS A CRITICAL OPERATIONAL ITEM AND POSES AN IMMINENT HEALTH HAZARD. THE OPERATOR CLOSED THE POOL AT THE TIME OF INSPECTION AND CALLED HIS SUPERVISOR FOR DIRECTION. DO NOT OPERATE THE POOL UNTIL THE FREE CHLORINE LEVEL IS AT LEAST 1 PPM. Correct By: 08-Jun-2023
3701-31-04 (B)(3) / Staff is trained and knowledgeable
Staff was not trained or knowledgeable in pool operations. Life guards did not know the required free chlorine level.
Train staff in pool operations, operation of equipment, chemical storage, use and handling and appropriate emergency procedures.
STAFF RESPONSIBLE FOR TESTING THE CHEMICAL LEVELS OF THE POOL MUST BE KNOWLEDGEABLE OF THE CRITICAL OPERATIONAL ITEMS. Correct By: 08-Jun-2023
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request.
TEST AND RECORD ALKALINITY AND CYANURIC ACID WEEKLY. Correct By: 14-Jun-2023
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Weirs in the skimmers not functioning properly.
All equipment must be maintained in accordance with the manufacturers specifications.
REPOSITION THE WEIRS IN THE SKIMMERS AND REDUCE THE WATER LEVEL. Correct By: 14-Jun-2023
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP ON THE FILTER BACKWASH DRAIN.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR FLOW METER. Correct By: 14-Jun-2023
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 12-June-2023
Comments |
---|
pool is not open |