3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week. Correct By: 09-Jul-2019
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat There is a large gap (greater than 4 inches) between the fence and the ground - by the "No SMOKING" sign.
FIX THE FENCE SO THAT THERE IS LESS THAN A 4 INCH GAP UNDER THE FENCE. CHECK THE FENCE BY THE NO SMOKING SIGN. Correct By: 09-Jul-2019
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The gate doe not self-close.
ADJUST THE SPRING ON THE GATE SO THAT THE GATE WILL SELF-CLOSE. Correct By: 09-Jul-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 02-July-2019
Comments |
---|
Our records show: The main drain suction outlet cover (Waterway 640-479xV) was installed 7/1/2018. The cover has a 7 year life span and must be replaced before 7/1/2025. -Post "DANGER: POOL CLOSED" sign on the fence/gate at the end of the season and at the end of the day. -Repaint the depth marking and NO DIVING markings on the deck before the start of next season. |