3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The equalizer outlets on the pool wall are not plugged and they do not have a compliant covers.
INSTALL VGB COMPLIANT COVERS OVER THE EQUALIZER OUTLETS OR PLUG THE OUTLETS AT THE POOL WALL.
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records. Sundays and Tuesdays, chemical testing is NOT recorded.
All facility records must be maintained and available for review upon request.
TEST THE WATER EVERY 4 HOURS EVERY DAY THAT THE POOL IS OPEN, SUNDAYS AND TUESDAYS INCLUDED. Correct By: 10-May-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 07-May-2018
Comments |
---|
The operator was observed performing onsite chemical tests and is aware of the acceptable parameters and necessary corrective actions. CAPS SHOULD BE USED ON THE TEST CELLS when mixing for the chlorine and pH tests. The total chlorine was NOT TESTED. TESTING MUST INCLUDE TESTS FOR FREE, COMBINE, AND TOTAL CHLORINE AS WELL AS ALKALINITY. The operator was NOT observed performing tests for Safety Vacuum Release System function. To ensure proper testing the HD should observed the operator testing the SVRS. It is recommended that the test kit for the indoor pool be a FAS DPD type kit. This type of test can measure combine chlorine at .2 ppm, where as the regular DPD test can only test to .5 ppm and only when the free chlorine is 1.5 ppm or lower. |