3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 03-Aug-2023
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
OPERATOR AND POOL COMPANY WERE CALLED TO NOTIFY OF THE IMMINENT HEALTH HAZARD AND TO CLOSE THE POOL UNTIL CRITICAL VIOLATIONS ARE CORRECTED. Correct By: 03-Aug-2023
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Gates or doors were not self-closing and lockable.
Repair gates or doors in order to be self-closing and lockable.
ADJUST GATE SO IT SELF-CLOSES.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 05-Aug-2023
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST ALKALINITY Correct By: 05-Aug-2023
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
ADJUST CYA Correct By: 05-Aug-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 03-August-2023