3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Weirs in the 2 skimmers in the shallow area stick.
All equipment must be maintained in accordance with the manufacturers specifications.
ADJUST THE WEIRS IN THE 2 SKIMMERS IN THE SHALLOW END SO THAT THEY FLOAT FREELY WITH THE WATER LEVEL. Correct By: 30-Jun-2022
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. Hose bib in the equipment room is not backflow protected.
Remove all cross connection hazards from the pool area.
INSTALL A BACKFLOW PREVENTER (ASSE 1011 VACUUM BREAKER) ON THE HOSE BIB LOCATED IN THE EQUIPMENT ROOM. Correct By: 30-Jun-2022
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FOUNTAIN FLOW METER. Correct By: 30-Jun-2022
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gates or doors were not self-closing and self-latching. Gate latch was locked, making the unable to latch.
Repair gates or doors in order to be self-closing and lockable.
KEEP THE GATE ON THE WOMEN'S REST-ROOM SIDE EITHER UNLOCKED SO THAT THE GATE WILL LATCH AFTER OPENING OR KEEP THE GATE LOCKED SO IT CANNOT BE OPENED. Correct By: 24-Jun-2022
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH. Correct By: 25-Jun-2022
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 23-June-2022
Comments |
---|
HAVE THE BACKFLOW PREVENTER INSPECTED ANNUALLY. CHECK WITH THE 9-1-1 OPERATOR TO ENSURE THEY HAVE THE CORRECT ADDRESS. When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm Safety Data Sheets (SDS) were not found in the equipment room, but Personal Protective Equipment (PPE), chemical gloves and goggles, are available for handling chemicals. The Certificate of Compliance for the main drain cover(s) is/are available in the equipment room. Our records show that the main drain suction outlet covers (Lawson MLD SG 1212) were installed 9-3-18. The covers have a 10 year life span and must be replaced before 9-3-28. The operator was observed performing onsite chemical tests appropriately and is aware of the acceptable parameters and necessary corrective actions. |