3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool.
SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION FOR THE REPLACEMENT OF THE PUMP AND THE CHLORINATOR. THE HAYWARD SP2615X20 1.5 HP WAS REPLACED WITH A HAYWARD SP2607X7 .75 HP PUMP. THE RAINBOW 300-29X EROSION FEEDER WAS REPLACED WITH A STENNER 45M5 PUMP FEEDER. Correct By: 11-Aug-2020
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 17-Aug-2020
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
ADJUST THE CYANURIC ACID Correct By: 11-Aug-2020
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 18-August-2020