[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm. INCREASE THE ALKALINITY. Correct By: 22-Dec-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 20-December-2023