3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met. Flow meter reading at 375 - minimum required flow rate is 635 (per volum of pool/turnover rate).
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 18-July-2017