3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
SVRS/APSOS/ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.
TEST SVRS MONTHLY AND RECORD ON THE WEEKLY OPERATIONAL SHEETS Correct By: 29-Jul-2019 3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE ALKALINITY Correct By: 29-Jul-2019 3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
RECORD MONTHLY ACC FLOW SWITCH TEST ON THE WEEKLY OPERATIONAL SHEET Correct By: 29-Jul-2019
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 26-July-2019