3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Backflow prevention devices were not maintained to function properly. The is no back flow protection one 2 hose bibs.
Have the backflow prevention device evaluated or replaced so that backflow is prevented.
INSTALL 2 ADDITIONAL ASSE 1011 BACKFLOW PREVENTERS ON 2 NEWLY IDENTIFIED HOSE BIBS. ONE IS IN THE FILTER ROOM BY THE WADING POOL FILTER AND THE OTHER IS ON THE OUTSIDE OF THE FILTER ROOM ON THE EAST SIDE OF THE BUILDING. Correct By: 04-Aug-2017
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 14-July-2017
Comments |
---|
The maximum allow filter flow is 548 gpm per ODH who allow 20 gpm per sf of filter area. THE MAX FLOW PER DRAIN COVER IS 515 GPM. ENSURE THAT THE FLOW NEVER EXCEEDED 515 GPM. ALSO CHANGE THE MAX FLOW RATE MARKED OF THE PIPE IN THE FILTER ROOM TO 515 GPM. PLEASE NOTE HANDOUT ON DEPTH MARKINGS AND "NO DIVING" SIGNS FOR FUTURE REFERENCE. |