3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. The hose bib in the filter room and the hose bib by the outside shower are not backflow protected.
Remove all cross connection hazards from the pool area.
INSTALL A BACK FLOW PREVENTER (ASSE 1011) ON THE HOSE BIB IN THE FILTER ROOM AND ON THE HOSE BIB BY THE OUTSIDE SHOWER. Correct By: 15-Jun-2018
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps. The flow meter was not working.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
REPAIR THE FLOW METER. Correct By: 15-Jun-2018
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. Depth markings and "No Diving" signs are more than 25 ft apart.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
APPLY MORE DEPTH MARKINGS AND "NO DIVING" MARKINGS SO THEY ARE NOT ANY MORE THAN 25 FT APART.. Correct By: 15-Jun-2018
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly.
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE ACC MONTHLY Correct By: 01-Jun-2018
3701-31-04 (E)(3)(c) / Location of emergency telephone posted when the phone is not visible.
Sign indicating the location of the emergency device (telephone) was not provided and emergency device was not visible in the pool area.
Ensure that a sign informing patrons of the location of the emergency device is always visible in the pool area.
POST A SIGN INDICATING THE LOCATION OF THE EMERGENCY PHONE. Correct By: 15-Jun-2018
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 07-June-2018