Inspection Information | Facility Name: | Pirate's Club Condos Swimming Pool |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 21-May-2019 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(f) Repeat The rate of flow was found to be below the minimum required rate to produce the 8 hour pool volume turnover. Rate was measured at 50 gpm and the required level is 71 gpm. Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. |
Comments |
---|
Water clarity is good - main drain covers visible. Good chemical levels. Safety equipment provided. Test log sheets provided. |