Inspection Information
Facility Name: Westlake Apartments
Facility Type: Pool
[?] Inspection type: Standard
Inspection date: 25-May-2017
Violations: A summary of the violations found during the inspection are listed below.
3701-31-04 (B)(6)(h)
Required meters and gauges were not maintained or were not functional while the pool is in operation. The flow meter was maxxed out- bobber possibly stuck? Or just not reading correctly - showing a rate of about 80 gpm.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation.
Comments
I will send you an Equipment Replacement Notification form to fill out regarding the new chlorine feeder.

If the flow meter is still reading too high after trying out a new one, the pump might need to be throttled back. The rate of flow cannot exceed 63 gpm for proper operation of the filter.