Inspection Information | Facility Name: | Kozy Kampground Swimming Pool |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 16-July-2018 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(h) Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation. (flow meter) Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation. |
Comments |
---|
Thank you for refreshing the depth markings! Good job on the record keeping of your daily testing. Keep working with the flow meter to keep the bobber un-stuck. Operator reported having to take the meter off weekly to clean due to the hard water/ rust causing the bobber to become lodged. There was a bottle of "The Works" cleaner there for that purpose. Operator reported a typical flow rate of around 100 gpm. If that is the case, then it is flowing too fast. The filter is only rated for a maximum flow of 63 gallons per minute. Gate was working great! |