Inspection Information
Facility Name: Bryson Swimming Pool
Facility Type: Pool
[?] Inspection type: Standard
Inspection date: 15-July-2016
Violations: A summary of the violations found during the inspection are listed below.
3701-31-04 (B)(6)(f)
Required turnover rates were not met. Flow meter measured at a rate of 935 gpm, which is below the required rate of 1381.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. Correct By: 16-Jul-2016
3701-31-04 (C)(2)
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. Correct By: 16-Jul-2016
3701-31-04 (C)(3)
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm. Correct By: 16-Jul-2016