Inspection Information | Facility Name: | Kozy Kampground Swimming Pool |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 23-May-2019 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(i) A means of determining rate-of-flow was not in working condition. Properly install a flow meter or have a pump curve available for every water pump used for the pool. |
3701-31-04 (B)(6)(q) Depth markers/deck warning signs were being refreshed - at the present time they were painted over. Operator stated he would have them completed prior to opening. Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. |
3701-31-04 (B)(6)(s) Gates or doors were not self-closing and lockable. Repair gates or doors in order to be self-closing and lockable. |
3701-31-04 (E)(2)(b)(i) A USCG Type IV personal flotation device with 30 - 60 foot throw line was not provided at the guarded pool. (Flotation device was provided, but the 30 ft. line was not.) Provide the personal floatation device components at the pool at all times. |
3701-31-04 (E)(2)(d) First aid equipment was damaged. Please replace with fresh - including disposable gloves. Provide first aid equipment, including a first aid kit, at the pool at all times. |
Comments |
---|
The disinfection feeder appeared to be new this year - the model number I had on file did not match what I observed out in the equipment building. Please complete an equipment replacement form and provide to me. I will send the form in a seperate email. The gate did not self-close and self latch. I wonder if the wind catches the signs that are attached to the gate door. Maybe the signs could be placed alongside the gate so that they don't interfere with the gate closing on windier days. Also, the spring might be able to be adjusted to have more tension to pull the door closed better. The ring buoy was not out at the pool yet, but was in the equipment building. The rope that goes along with the buoy is not long enough. The rule requires at least 30 ft. of rope. The depth markings are being refreshed. Please make sure this is done prior to opening. The flow meter was not working at the time of inspection. Please replace with a fresh one so that the flow can be monitored. This is important as it tells whether the pool water is begin filtered effectively. The first aid kit contents looked to be damaged from exposure to moisture. Please replace with a fresh kit - including disposable gloves. |