Inspection Information | Facility Name: | Kozy Kampground Swimming Pool |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 25-May-2017 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(i) A means of determining rate-of-flow was not found for all water pumps. Properly install a flow meter or have a pump curve available for every water pump used for the pool. |
Comments |
---|
Flow meter was not working - bobber was stuck at the bottom. Operator stated that he would repair. Vac-Alert is going to be tested by Chris. Fence is going to be adjusted so that the gate is self closing and latching. Adjust pH to at least 7.2 - 7.8. Adjust alkalinity to at least 60 ppm. |