Inspection Information
Facility Name: Kozy Kampground Swimming Pool
Facility Type: Pool
[?] Inspection type: Standard
Inspection date: 25-May-2017
Violations: A summary of the violations found during the inspection are listed below.
3701-31-04 (B)(6)(i)
A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
Comments
Flow meter was not working - bobber was stuck at the bottom. Operator stated that he would repair.

Vac-Alert is going to be tested by Chris.

Fence is going to be adjusted so that the gate is self closing and latching.

Adjust pH to at least 7.2 - 7.8. Adjust alkalinity to at least 60 ppm.