Inspection Information
Facility Name: Pirate's Club Condos Swimming Pool
Facility Type: Pool
[?] Inspection type: Standard
Inspection date: 30-July-2018
Violations: A summary of the violations found during the inspection are listed below.
3701-31-04 (B)(6)(f)
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
Comments
Recently the facility obtained approval from ODH to install a salt chlorine generator as the primary disinfecting device. It is functioning and is producing chlorine at proper levels.

At the time of inspection, the report could not be generated due to the facility being "locked" by ODH because of the plan review issue. After resolving that issue, and being able to open the record to complete the report, I noticed that the minimum required flow rate is supposed to be 71 gpm. We looked at the flow meter and found it to be at 40 gpm. Please check into this and see if it can be adjusted to be in line with the required rate.