Inspection Information | Facility Name: | St. Henry Pool |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 16-August-2022 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(4)(a)(ii) Combined chlorine was not tested daily at pool side prior to use. Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use. |
3701-31-04 (B)(4)(a)(vi) Total alkalinity was not tested weekly. Test total alkalinity at least once/week. |
3701-31-04 (C)(2) pH was outside the range of 7.2 to 7.8. Treat the pool water so that the pH is within the acceptable range. |
3701-31-04 (C)(3) Total alkalinity was less than 60 ppm. Raise the total alkalinity to at least 60 ppm. |
Comments |
---|
The testing record sheets could have some more consistent / clear markings as to the dates that the data are referring to. Also, there were some testing parameters that are not being done / recorded - see observations section for more information. |