Inspection Information | Facility Name: | Lincoln Community Center |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 15-April-2024 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(c)(ii) Observed the backwash discharge pipes from the filters without an air gap. Provide an air gap between the filter discharge pipes and the drain. |
3701-31-04 (E)(2)(e) At the time of inspection, the emergency device was observed non functional. To ensure authorities are able to be contacted during an emergency, the emergency device shall be functional. Repair or replace. As a temporary fix, place a sign adjacent to device indicating device is nonfunctional, and post a sign or signs indicating the emergency telephone is located at the front desk. Then, ensure emergency telephone number(s) are posted at the front desk. |
Comments |
---|
- Observed deterioration in the grout on the steps leading to the men's bathroom. Remove grout and replace. - At the time of inspection, all the water quality readings were observed within normal limits. - Inspection was conducted with Shane Snapp and Courtney Long. |