Inspection Information | Facility Name: | Lincoln Community Center |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 27-October-2017 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (C)(2) At the time of inspection, the pH was observed at 7.0. For chlorine to properly disinfect the pool, the pH shall be between 7.2 and 7.8. Increase the pH of the pool. Also, ensure the automatic chemical controller pH reading is calibrated so it corresponds with the pH reading of the pool. |
Comments |
---|
- At the time of inspection, all the safety equipment was present and in good repair. - Reinspection will be conducted on or after 11/02/2017. |