Inspection Information
Facility Name: Village of Concord
Facility Type: Pool
[?] Inspection type: Standard
Inspection date: 07-July-2020
Violations: A summary of the violations found during the inspection are listed below.
3701-31-04 (B)(1)(e)
Critical At the time of inspection, the automatic chemical controller was observed at 777 while the free chlorine was observed at 18.6 ppm. To ensure the pool is properly disinfected, the ACC shall function properly and probes be calibrated according to the readings in the pool. Repair or replace the automatic chemical controller.

3701-31-04 (B)(4)
Repeat At the time of inspection, the records for the testing of water quality, the automatic chemical controller and any chemicals added were not observed. Ensure the records are being maintained and on hand.

3701-31-04 (B)(4)(a)(i)
Repeat At the time of inspection, testing of the free chlorine was observed either not being tested or documented. With an automatic chemical controller, test the free chlorine every 12 hours (prior to opening) and document.

3701-31-04 (B)(4)(a)(ii)
Repeat At the time of inspection, the combined chlorine was observed either not being tested or documented. Test combined chlorine daily and document.

3701-31-04 (B)(4)(a)(iii)
Repeat At the time of inspection, the pH was observed either not being tested or documented. Test the pH daily and document.

3701-31-04 (B)(4)(a)(iv)
Repeat At the time of inspection, water temperatures were observed either not being tested or documented. Test and document the water temperature daily.

3701-31-04 (B)(4)(a)(vi)
Repeat At the time of inspection, the total alkalinity was observed either not being tested or documented. Test alkalinity once a week and document.

3701-31-04 (B)(4)(c)
Repeat The documentation of the testing of the automatic chemical controller flow switch was not observed. Ensure it is being tested monthly and document.

3701-31-04 (E)(2)(e)
Repeat At the time of inspection, the emergency telephone sign was observed not functioning properly. Repair or replace the emergency telephone.

3701-31-04 (E)(3)(b)
At the time of inspection, the "Swimming Alone is Not Recommended" sign was not observed. Provide the sign and post.

Comments
- Reinspection will be conducted after the automatic chemical controller is repaired or replaced.