Inspection Information | Facility Name: | Tipp Aquatic Center (Activity) |
---|---|
Facility Type: | Special Use Pool |
[?] Inspection type: | Standard |
Inspection date: | 01-June-2023 |
No violations were documented at the time of inspection. |
Comments |
---|
Facility not operating at time of inspection. Oxygen Reduction Potential (ORP) observed at 640 mv at time of inspection. Ensure pool chemistry readings are taken every 4 hours while the facility is in operation until the Automatic Chemical Controller (ACC) has an ORP value that reads above 650. Swimsafe Pool Vice President stated that ACC probes will be replaced to fix the low ORP value. |