Inspection Information | Facility Name: | Towne Park Apartment |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Follow-up |
Inspection date: | 01-July-2019 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (C)(3) Repeat At the time of inspection, the alkalinity was observed at 30 ppm. The alkalinity shall be at or above 60 ppm to ensure the water is balanced. Increase the chlorine and pH and then increase the alkalinity to at least 60 ppm. |
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (C)(2)/pH is within 7.2 to 7.8 At the time of inspection, the pH was observed below 7.0. For the chlorine to properly disinfect the pool the pH shall be between 7.2 and 7.8. Once the chlorine is above 1.0 ppm, increase the pH, if necessary. |
Comments |
---|
- Reinspection was conducted to check the status of the water quality readings. At the time of inspection, the free chlorine was observed at 2.4 ppm with a combined chlorine of 0.4. The pH was observed at 7.2. Ensure the pH is between 7.2 and 7.8. The alkalinity was still observed at 40 ppm (see violation). The remaining violation will be checked during the next standard inspection. |