Inspection Information | Facility Name: | Comfort Inn |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 08-September-2022 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(1)(a) Critical Repeat Observed main drain cover not secure as required. Upon informing the operator, the pool was voluntarily closed. Keep the pool closed until the main drain cover is secure and a representative from MCPH can verify. |
3701-31-04 (C)(3) Total alkalinity was less than 60 ppm. Observed total alkalinity of 30 ppm. Raise the total alkalinity to at least 60 ppm. |
Comments |
---|
Upon inspection, the main drain cover was observed not secure. After informing the operator, the pool was voluntarily closed. Please keep the pool closed until the main drain cover can be adequately secured and contact MCPH for a re-inspection to verify. If MCPH is not contacted by 9/14/22, a re-inspection will occur on or after 9/15/22. Inspection conducted with Shelley Myers. |