Inspection Information | Facility Name: | Hampton Inn By Hilton |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 08-March-2024 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 ( D )(6)(a) Repeat At the time of inspection, the oxygen reduction potential was observed at 630 mV. To ensure the free chlorine is at or above 1.0 ppm, the ORP shall be at or above 650 mV. Have the automatic chemical controller evaluated to ensure accurate ORP readings. |
3701-31-04 (B)(4)(c) Repeat At the time of inspection, the automatic chemical controller and safety vacuum release system testing were not being documented on a monthly basis. To ensure proper function, ensure the ACC and SVRS are tested and documented on a monthly basis. |
3701-31-04 (B)(6) Repeat At the time of inspection, the flow meter was observed at reading at 70 gallons per minute that exceeds the filter maximum flow rate. Evaluate the system and ensure the flow does not exceed the filter maximum filter flow rate of 62 gpm. |