Inspection Information | Facility Name: | Comfort Inn |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Follow-up |
Inspection date: | 09-September-2022 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(p) Deck surfaces had standing water or other hazards. Observed large chips in the deck surface. Repair areas of the deck where standing water is occuring. If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval. |
3701-31-04 (C)(2) pH was outside the range of 7.2 to 7.8. Observed a pH of 7.0 Treat the pool water so that the pH is within the acceptable range. |
3701-31-04 (C)(3) Repeat Total alkalinity was less than 60 ppm. Observed total alkalinity of 30 ppm. Raise the total alkalinity to at least 60 ppm. |
3701-31-04 (E)(3)(b) The unguarded pool was in use without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted. Post the "Children must be supervised" and/or "Swimming Alone is Not Recommended" signs at all times the pool is available for use. Use exact terminology as shown above. |
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(1)(a)/Outlet covers shall be installed/secured/in compliance Observed main drain cover not secure as required. Upon informing the operator, the pool was voluntarily closed. Keep the pool closed until the main drain cover is secure and a representative from MCPH can verify. |
Comments |
---|
Upon re-inspection, the main drain cover was observed secure. Continue checking that the main drain cover is secure frequently. Pool residuals satisfactory at time of re-inspection. |