Inspection Information | Facility Name: | Tipp Aquatic Center (Activity) |
---|---|
Facility Type: | Special Use Pool |
[?] Inspection type: | Standard |
Inspection date: | 24-June-2021 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 ( D )(6)(a) Repeat At the time of inspection, the oxygen-reduction potential was observed at 570 while the free chlorine was observed at 3.6 ppm. To ensure there is enough disinfectant in the pool, the ORP shall be at or above 650. Evaluate the probes or automatic chemical controller to ensure they are functioning properly and increase ORP. |
3701-31-04 (B)(3) At the time of inspection, the pool manager was unable to test no flow on the automatic chemical controller. To ensure proper function of equipment, pool staff shall be properly trained on equipment operation. Ensure managers are trained in pool operations, operation of equipment, chemical storage, use and handling and emergency procedures. |
Comments |
---|
- Prior to opening, ensure the ACC is functioning properly and the free chlorine is at or above 1.0 ppm. Also, ensure the ACC no flow is tested monthly and documented. - At the time of inspection, all the safety equipment was present and in good repair. |