Inspection Information | Facility Name: | Troy Aquatic Park (Wading Pool) |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 20-July-2022 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 ( D )(6)(a) ORP reading was below 650 mv. Observed ORP reading between 580 and 640 mv. Have the ACC unit inspected to determined why the ORP is low. |
3701-31-04 (C)(2) pH was outside the range of 7.2 to 7.8. Observed pH of 8.0 Treat the pool water so that the pH is within the acceptable range. |
Comments |
---|
Automatic chemical controller tested and functional upon inspection. Inspection conducted with Shelly Myers. |