Inspection Information | Facility Name: | Baymont Inn & Suites |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 21-April-2022 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(4)(a)(i) According to the records, the chlorine was observed not being tested prior to opening. To ensure proper chlorine level, test the water prior to opening and every 12 hours. |
3701-31-04 (B)(4)(a)(ii) According to the records, the combined chlorine was observed not being tested prior to opening. Ensure the combined chlorine is tested prior to opening and every 12 hours. |
3701-31-04 (B)(4)(a)(iii) According to the records, the pH was not being tested prior to opening. To ensure the pH is within normal range, test the water prior to opening and every 12 hours. |
3701-31-04 (B)(6)(c)(ii) At the time of inspection, the backwash lines was observed without an air gap. Place an air gap between the backwash lines and drain. |
3701-31-04 (B)(6)(j) Critical At the time of inspection, the operator was unable to test the safety vacuum release system. To ensure the SVRS is functioning properly, ensure it is tested and documented monthly. Determine how to test the SVRS. |
3701-31-04 (D)(7)(c) Critical At the time of inspection, the operator was unable to test the automatic chemical controller to determine if the audile or visual alarm is functional. To ensure the ACC is functioning properly, the operator shall test and document the unit. Determine how to test the ACC. |
3701-31-04 (E)(3)(c) At the time of inspection, a sign indicating the location of the emergency telephone was not present. If the emergency telephone is not visible in the pool area, place a sign indicating where the emergency telephone is located. |
Comments |
---|
- At the time of inspection, the operator was unable to test the safety vacuum release system and automatic chemical controller (see violation). Because of this, the operator voluntarily closed the pool. Continue to cease operation of the pool until the SVRS and ACC are able to tested. Contact the health department when able to test both units. Reinspection will be conducted at that time. - Inspection was conducted with Carson Richardson. |