Inspection Information | Facility Name: | Dolphin Club (Wading) |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 07-July-2023 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(h) At the time of inspection, the flow meter was observed nonfunctional. To ensure proper flow, the flow meter shall be functional. Repair or replace. |
3701-31-04 (E)(3)(b) At the time of inspection, the "swimming alone is not recommended" or similar sign was not observed. Post a sign stating "swimming alone is not recommended" or similar. |
Comments |
---|
- At the time of inspection, the automatic chemical controller (ACC) was observed being by-passed. According to the operator, the ACC was being by-passed due to not knowing how to function it. The records indicated the pool was being tested every 2 hours while the operator stated the water quality is tested every hour. At the time of inspection, all the water quality readings were within normal limits and the safety equipment was on hand. |