Inspection Information | Facility Name: | Comfort Inn & Suites |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 25-July-2023 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(4)(c) Repeat At the time of inspection, according to the records provided, the safety vacuum release system and automatic chemical controller were observed not being tested/documented as required. To ensure proper function, the SVRS and ACC shall be tested and documented monthly. During the inspection, the owner properly tested both the SVRS and ACC. |
Comments |
---|
At time of inspection the ORP level was reading 575. After discussing with the operator, the facility will take chemical readings every 4 hours while the facility is open until the ORP reads >650 and the inspector observes this. Consider probe replacement as the Automatic Chemical Controller (ACC) also had a pH reading that did not reflect what was tested with the DPD-Test Kit. Ensure ACC and Safety Vacuum Release System (SVRS) are both tested monthly and test results recorded. A reinspection will occur on or after |