Inspection Information
Facility Name: Comfort Inn & Suites
Facility Type: Pool
[?] Inspection type: Standard
Inspection date: 25-July-2023
Violations: A summary of the violations found during the inspection are listed below.
3701-31-04 (B)(4)(c)
Repeat At the time of inspection, according to the records provided, the safety vacuum release system and automatic chemical controller were observed not being tested/documented as required.
To ensure proper function, the SVRS and ACC shall be tested and documented monthly. During the inspection, the owner properly tested both the SVRS and ACC.
Comments
At time of inspection the ORP level was reading 575. After discussing with the operator, the facility will take chemical readings every 4 hours while the facility is open until the ORP reads >650 and the inspector observes this. Consider probe replacement as the Automatic Chemical Controller (ACC) also had a pH reading that did not reflect what was tested with the DPD-Test Kit.

Ensure ACC and Safety Vacuum Release System (SVRS) are both tested monthly and test results recorded.

A reinspection will occur on or after