Inspection Information | Facility Name: | Towne Park Apartment |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 23-May-2018 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(1)(a) Critical At the time of inspection, the VGB cover on the northeast equalizer line was observed loose not secured. To prevent any hazards, all outlet covers shall be secured and installed properly. Secure or replace the cover. |
3701-31-04 (B)(1)(c) Critical At the time of inspection, the free chlorine was observed at 0.8 ppm. To disinfect the pool, the chlorine residual shall be at or above 1.0 ppm. Increase the free chlorine to ensure there is a residual of 1.0 or above. |
3701-31-04 (B)(1)(e) Critical At the time of inspection, the ORP of the automatic chemcial controller was observed at 850 while the free chlorine was observed at 0.8 ppm. To ensure proper disinfection and pH levels, the ACC shall be maintained in good repair. Repair or replace the ACC. |
3701-31-04 (B)(1)(l) Critical At the time of inspection, the underwater lights and pump room equipment were not observed on a GFI breaker or outlet. To prevent electrical hazards, place the underwater lights and pump room equipment on a GFI. |
3701-31-04 (C)(2) At the time of inspection, the pH was observed at 7.0. To ensure the chlorine properly disinfects the pool, the pH shall be between 7.2 and 7.8. Increase the pH of the pool. |
3701-31-04 (C)(3) At the time of inspection, the alkalinity was observed at 40 ppm. To ensure the pool water is balanced, the alkalinity shall be at or above 60 ppm. Increase the alkalinity of the pool. |
Comments |
---|
- Ensure all the skimmers are equipped with skimmer baskets and weirs. Also, ensure new reagents are obtained. |