Inspection Information | Facility Name: | Hampton Inn By Hilton |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 26-July-2023 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 ( D )(6)(a) At the time of inspection, the oxygen reduction potential (ORP) was observed at 642. To ensure the chlorine meets the rule requirement, ensure the ORP is at or above 650. |
3701-31-04 (B)(4)(c) Upon reading the records provided, the testing of the safety vacuum release system (SVRS) and automatic chemical controller (ACC) were observed not being tested and recorded. To ensure the ACC and SVRS are working properly, the ACC and SVRS shall be tested and documented monthly. |
3701-31-04 (B)(6)(h) At the time of inspection, the flow meter was observed not functioning properly. To ensure proper flow and thus turnover rate, ensure the flow meter is functioning properly. |
3701-31-04 (E)(2)(a)(ii) At the time of inspection, the ring buoys were observed without 30-60 ft throw line attached. Ensure the ring buoy has the throw line attached. |