Inspection Information | Facility Name: | Tipp Aquatic Center (Spray Ground) |
---|---|
Facility Type: | Special Use Pool |
[?] Inspection type: | Standard |
Inspection date: | 21-August-2023 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(f) Repeat At the time of inspection, the flow meter was observed at 75 gallons per minute (gpm) with a calculated turnover rate of 51 minutes. To ensure the turnover rate meets the requirement of 30 minutes, the flow rate shall be at or above 127 gpm. Evaluate the system and ensure the flow is met. |
Comments |
---|
- The free chlorine of a sprayground shall be at or above 2.0 parts per million. Ensure the free chlorine meets this requirement. If any corrective actions are completed, ensure they are documented. - At the time of inspection, all the water quality readings were observed within normal range. - Inspection was conducted with Brittney Holbrook. |