Inspection Information | Facility Name: | Towne Park Apartment |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Follow-up |
Inspection date: | 07-August-2017 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(1)(a) Critical Repeat At the time of inspection, the equalizer line cover closest to the steps was observed not secured. To prevent entrapment hazards, all covers shall be secure and in compliance. Cease operation of the pool and secure the equalizer line cover. |
3701-31-04 (B)(1)(c) Critical Repeat The free chlorine or chlorine residual was observed at 0.2 ppm. To disinfect the pool, the chlorine residual shall be at or above 1.0 ppm. At the time of inspection, the pool was voluntarily closed. Ensure the free chlorine is at or above 1.0 ppm. |
3701-31-04 (B)(1)(e) Critical Repeat The automatic chemical controller was observed reading an ORP of 740 while the free chlorine was observed at 0.2 ppm. To ensure the chlorine maintains a proper reading, the automatic chemical controller shall be maintained in good repair. Cease operation of the pool until the ACC is repaired or replaced. |
3701-31-04 (C)(2) Repeat At the time of inspection, the pH was observed at 8.0. For the chlorine to properly disinfect the pool, the pH shall be between 7.2 and 7.8. Decrease the pH of the pool to within normal limits. |
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (C)(3)/Total alkalinity is at or greater than 60 ppm The alkalinity was observed at 40 ppm. To ensure the pool is properly balanced, the alkalinity shall be at or above 60 ppm. Once the free chlorine and pH are within normal limits, add sodium bicarbonate to the pool to increase the alkalinity. |
Comments |
---|
- Cease operation of the pool until the violations have been corrected and an inspection is conducted. Once the violations have been corrected, contact the health department (Jason Dreier) at 937-573-3506. |