Inspection Information | Facility Name: | Towne Park Apartment |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 27-May-2022 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(1)(c) Critical Repeat At the time of inspection, the free chlorine was observed at 0.8 ppm. To properly disinfect the pool, the free chlorine shall be at or above 1.0 ppm. At the time of inspection, the pool had yet to be opened for the season. Keep up the pool closed until the free chlorine is at or above 1.0. |
3701-31-04 (B)(1)(e) Critical At the time of inspection, the automatic chemical controller was observed with an ORP of 830 while the chlorine was observed at 0.8. To ensure the proper chlorine and pH readings, the ACC shall be functioning properly. Prior to opening, ensure the automatic chemical controller is functioning properly. |
3701-31-04 (B)(6) At the time of the inspection, two of the skimmers were observed without weirs (flaps). To allow for proper surface filtering, install weirs. |
3701-31-04 (B)(6)(c)(ii) In the pump room, the backwash line was observed without an air gap. Place a two to four inch air gap between the backwash line and drain. |
Comments |
---|
- At the time of inspection, all safety equipment was present and in good repair. - Reinspection will be conducted on or after 6/1/22 to check not only the chlorine but also the automatic chemical controller. |