Inspection Information | Facility Name: | Fairfield Inn |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 22-March-2019 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6) Equipment was not maintained per manufacturers specifications. Please see comments below regarding main drain function All equipment must be maintained in accordance with the manufacturers specifications. |
Comments |
---|
-Main drain not currently working properly. SVRS was tested and is working properly. We believe the main drain valve is stripped or stuck so that main drain cannot be turned off or on. We believe it is currently stuck in the "off" position. -Water chemistry was tested and is within acceptable parameters Inspection conducted with: Shane Snapp |