Inspection Information | Facility Name: | Rolling Hills Camp |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 24-May-2019 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(1)(d) Critical Observed main drains were not functioning properly. Two main drains exist in pool, PIC stated that they do not actually function and all of there circulation is achieved through the skimmers. Within two weeks, have a specialist evaluate the system and determine why the main drains are not functioning and what must be repaired to ensure the circulation system is functioning per approved design and up to manufacturer's specifications |
3701-31-04 (E)(3)(c) Sign indicating the location of the emergency device (telephone) was not provided and emergency device was not visible in the pool area. Observed no sign indicating location of emergency phone Ensure that a sign informing patrons of the location of the emergency device is always visible in the pool area. |
Comments |
---|
Within two weeks, by June 7th, 2019, have a specialist evaluate the circulations system and determine what repairs need to be made to ensure that the system functions as approved and per manufacturer's specifications. The main drains need to function as intended |