Inspection Information | Facility Name: | Comfort Suites |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 25-July-2017 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(1)(c) Critical At the time of inspection, the free chlorine was observed at 0.0 ppm. In order to disinfect the pool, the free chlorine shall be at or above 1.0 ppm. At the time of inspection, the PIC voluntarily closed the pool. Ensure the free chlorine is at or above 1.0 ppm. |
3701-31-04 (B)(1)(d) Critical Upon entering the pump room, the pump was observed in disrepair - not functioning. To allow for proper circulation and disinfection, the pump shall be functioning properly. At the time of inspection, the PIC voluntarily closed the pool and was going to contact a professional for repairs or replacement. Contact the health department when repairs or replacement of the circulation system is completed. |
3701-31-04 (B)(6)(i) The flow meter was observed in disrepair - Not functioning. To ensure the proper rate of flow, a flow meter shall be functioning properly. Repair or replace the flow meter. |
3701-31-04 (C)(3) The alkalinity was observed at 50 ppm. For the pool to be properly balanced, the alkalinity shall be at or above 60 ppm. Add sodium bicarbonate to the pool to increase the alkalinity of the pool. |
3701-31-04 (E)(2)(e) In the pool area, an emergency telephone was not observed To contact assistance during an emergency, a telephone shall be provided. Provide an emergency telephone. |
3701-31-04(D)(6)(a)(2) Critical Observed the ORP of the automatic chemical controller at 554. For the free chlorine to be at or above 1.0 ppm, the ORP of the ACC shall be at or above 650. Increase the ORP of the ACC. |
Comments |
---|
- At the time of inspection, did not observe any patrons in or around the pool. - Contact the health department when repairs have been completed and all chemical readings are within normal range. Also, ensure the underwater lights are on a GFCI breaker, switch or outlet. - Inspection was conducted by both Jason Dreier and Shane Snapp. |