Inspection Information | Facility Name: | Tipp Aquatic Center (Spray Ground) |
---|---|
Facility Type: | Special Use Pool |
[?] Inspection type: | Standard |
Inspection date: | 30-June-2017 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(1)(e) Critical At the time of inspection, the automatic chemical controller ORP was observed reading 735 while the chlorine reading at the spray ground nozzle was observed at 100 ppm. The ensure the chlorine level is within normal limits, the automatic chemical controller shall be maintained in good repair. Cease operation of the spray ground until the ACC is repaired or replaced. |
3701-31-04 (C)(2) The pH was observed above 8.0. For the chlorine to properly disinfect the pool, the pH shall be between 7.2 and 7.8. Decrease the pH to within normal limits. |
Comments |
---|
- At the time of inspection, the total chlorine was observed at 100 ppm. This level was obtained through the use of pHydrion Micro Chlorine test strips normally used in the testing of chlorine concentrations seen in food service and retail food establishments. Because of the amount of chlorine in the spray ground, the pH and the automatic chemical controller not working properly, the spray ground was voluntarily closed. A reinspection will be conducted on 07/03/2017 to check the ACC and the water quality readings. |