Inspection Information | Facility Name: | Comfort Suites |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Follow-up |
Inspection date: | 03-July-2018 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(1)(c) Critical Repeat At the time of inspection, the free chlorine was observed at 0.2 ppm. For the pool to be properly disinfected, the free chlorine shall be at or above 1.0 ppm. Increase the free chlorine to at or above 1.0 ppm. |
3701-31-04 (B)(1)(e) Critical Repeat At the time of inspection, the ORP reading was observed at 722 and the free chlorine was observed at 0.2 ppm. To ensure proper chlorine concentration, the Automatic Chemical Controller shall be maintained in good repair. Repair or replace the ACC to ensure the ORP is at or above 650 and the free chlorine is at or above 1.0 ppm. |
3701-31-04 (C)(3) At the time of inspection, the alkalinity was observed at 40 ppm. To ensure the pool is properly balanced, the alkalinity shall be at or above 60 ppm. Increase the alkalinity of the pool. |
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 ( D )(6)(a)/ORP reading shall be 650 millivolts or greater. At the time of inspection, the ORP was observed at 388. To allow for proper chlorine concentration, the ORP shall be at or above 650. Increase the ORP. |
3701-31-04 (C)(2)/pH is within 7.2 to 7.8 At the time of inspection, the pH was observed at 7.0 To allow for the chlorine to properly disinfect the pool, the pH shall be between 7.2 and 7.8. Increase the pH of the pool to within normal limits. |
Comments |
---|
- Reinspection was conducted due to report dated 06/22/2018. At the time of inspection, the free chlorine was observed at 0.2 ppm even though the automatic chemical controller was reading 722. The PIC closed the pool. Continue to cease operation of the pool until a reinspection is conducted on 07/05/2018. Also, the alkalinity was observed at 40 ppm. All other water quality readings were within normal limits. During the reinspection, provide documentation of water quality readings. |