Inspection Information | Facility Name: | Comfort Suites |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Follow-up |
Inspection date: | 05-July-2018 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(1)(c) Critical Repeat At the time of inspection, the free chlorine was observed at 0.2 ppm. For the pool to be properly disinfected, the free chlorine shall be at or above 1.0 ppm. Increase the free chlorine to at or above 1.0 ppm. |
3701-31-04 (B)(1)(e) Critical Repeat At the time of inspection, the ORP reading was observed at 722 and the free chlorine was observed at 0.2 ppm. To ensure proper chlorine concentration, the Automatic Chemical Controller shall be maintained in good repair. Repair or replace the ACC to ensure the ORP is at or above 650 and the free chlorine is at or above 1.0 ppm. |
3701-31-04 (C)(3) Repeat At the time of inspection, the alkalinity was observed at 40 ppm. To ensure the pool is properly balanced, the alkalinity shall be at or above 60 ppm. Increase the alkalinity of the pool. |
Comments |
---|
- At the time of inspection, the pool was closed and the PIC stated the lines on the automatic chemical controller are scheduled to be changed on Monday, 07/09/2018. A reinspection will be conducted on or after 07/10/2018 to check the automatic chemical controller and water quality readings. |