Inspection Information | Facility Name: | YMCA Piqua Branch-Female Spa |
---|---|
Facility Type: | Spa |
[?] Inspection type: | Standard |
Inspection date: | 03-August-2023 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6) Equipment was not maintained per manufacturers specifications. Maximum flow rate of the filtration system was exceeded. Flow rate observed at 45 and maximum flow limit observed at 28. All equipment must be maintained in accordance with the manufacturers specifications. |
3701-31-04 (C)(3) Repeat Total alkalinity was observed at 50 ppm. Raise the total alkalinity to at least 60 ppm. |
3701-31-04 (E)(3)(c) Sign indicating the location of the emergency device (telephone) was not provided and emergency device was not visible in the pool area. Ensure that a sign informing patrons of the location of the emergency device is always visible in the pool area, and ensure that emergency numbers are posted for reference at the phone location. |