Inspection Information | Facility Name: | Tipp Aquatic Center (Spray Ground) |
---|---|
Facility Type: | Special Use Pool |
[?] Inspection type: | Standard |
Inspection date: | 02-June-2017 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(1)(c) Corrected During Inspection Critical Chlorine disinfectant residual was less than 2 ppm for the sprayground Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 2 ppm or above prior to placing the sprayground back into operation. |
3701-31-04 (B)(6) Repeat Equipment was not maintained per manufacturers specifications. Flow sensor on automatic controller was not operational. All equipment must be maintained in accordance with the manufacturers specifications. |
Comments |
---|
Ensure staff on site knows how to adjust the chemicals to keep pool operating at proper chemical levels. Close the pool if disinfectant levels drop below required concentrations. Pool was operating at 1.2 ppm chlorine when 2.0 ppm is the minimum. Automatic controller should be responding to such levels. |