Inspection Information
Facility Name: Towne Park Apartment
Facility Type: Pool
[?] Inspection type: Follow-up
Inspection date: 25-May-2018
Violations: A summary of the violations found during the inspection are listed below.
3701-31-04 (B)(1)(l)
Critical Repeat At the time of inspection, the underwater lights and pump room equipment were not observed on a GFI breaker or outlet.
To prevent electrical hazards, place the underwater lights and pump room equipment on a GFI.
3701-31-04 (C)(2)
Repeat At the time of inspection, the pH was observed at 7.0.
To ensure the chlorine properly disinfects the pool, the pH shall be between 7.2 and 7.8. Increase the pH of the pool.
The following violation(s) have been corrected since the last inspection.
3701-31-04 (B)(1)(a)/Outlet covers shall be installed/secured/in compliance
At the time of inspection, the VGB cover on the northeast equalizer line was observed loose not secured.
To prevent any hazards, all outlet covers shall be secured and installed properly. Secure or replace the cover.
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required.
At the time of inspection, the free chlorine was observed at 0.8 ppm.
To disinfect the pool, the chlorine residual shall be at or above 1.0 ppm. Increase the free chlorine to ensure there is a residual of 1.0 or above.
3701-31-04 (B)(1)(e)/Automatic Chemical Controller (ACC) shall function properly.
At the time of inspection, the ORP of the automatic chemcial controller was observed at 850 while the free chlorine was observed at 0.8 ppm.
To ensure proper disinfection and pH levels, the ACC shall be maintained in good repair. Repair or replace the ACC.
3701-31-04 (C)(3)/Total alkalinity is at or greater than 60 ppm
At the time of inspection, the alkalinity was observed at 40 ppm.
To ensure the pool water is balanced, the alkalinity shall be at or above 60 ppm. Increase the alkalinity of the pool.
Comments
- Reinspection was conducted due to report dated 05/23/2018. At the time of inspection, the free chlorine was observed at 1.0 ppm. Ensure the free chlorine is maintained at or above 1.0 ppm at all times. Also, the alkalinity was observed at 70 ppm. The pH was still observed at 7.0. The underwater lights were observed disconnected from power and according to the PIC the equipment in the pump room will be placed on a GFI breaker on June 5. The testing of the ACC flow had not yet been checked. This will be checked along with the GFI installation on or after 6/6/2018. Once the pH is increased to within normal limits (7.2 to 7.8), the pool is satisfactory to open for the season.

- Ensure the weirs are installed and new reagents are obtained.