Inspection Information | Facility Name: | Holiday Inn Express Troy |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 07-August-2023 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B) At the time of inspection, tiles located where the spa was located was observed in disrepair. Repair or replace the deck tiles to eliminate tripping and cutting hazards. |
3701-31-04 (B)(4)(a)(i) Repeat According to the records provided, the chlorine residual was observed not being tested prior to opening and every 4 hours. To ensure the free chlorine is at or above 1.0 ppm, the chlorine residual shall be tested prior to opening and every 4 hours. Test the free chlorine prior to opening and every 4 hours. |
3701-31-04 (B)(4)(a)(ii) Repeat According to the records provided, the combined chlorine was observed not being tested prior to opening and every 4 hours. Prior to opening and every 4 hours, to ensure the combined chlorine is at or below 1.0 ppm, the combined chlorine shall be tested. Test the combine chlorine prior to opening and every 4 hours. |
3701-31-04 (B)(4)(a)(iii) Repeat According to the records provided, the pH was observed not being tested prior to opening and every 4 hours. To ensure the pH is between 7.2 and 7.8, the pH shall be tested every prior to opening and every 4 hours. Test the pH prior to opening the pool and every 4 hours. |
Comments |
---|
- To prevent hazards, on the ladder in the 5 ft end, place an end cap on the bottom. - At the time of inspection, all the safety equipment was present and in good repair. Also, the water quality readings were observed within normal limits. - Inspection was conducted not only with Brittney Holbrook but also Taylor Munn. |